KA Series Chain drives
KA 34-BSY+
-
Can be used for openings for smoke ventilation; D+H Euro SHEV in accordance with EN 12101‑2; and for daily natural ventilation
-
With BSY+ motor and synchronised electronics controlled via microprocessor
-
High‑speed function (HS) for especially fast opening windows in case of fire (SHEV)
-
Option of up to 8 drives in one synchronous group
-
Supply and signals at KA 34‑BSY+ for up to 3 drives can be looped in series
-
Special chain stabilisation
-
Relief of pressure on window gasket after closing process
-
Programmable drive functions and different drive parameters
-
Running speed in CLOSED direction decreases to 5 mm/s (passive closing edge protection)
-
Time-controlled reversing when an obstacle is detected in the CLOSED direction (active closing edge protection)
Approvals / Certificates
Designs and technical data
KA-BSY+ | KA 34-BSY+ | KA 34/600-BSY+ R (M2) | KA 34/600-BSY+ L (S1) | KA 34/700-BSY+ R (M2) | KA 34/700-BSY+ L (S1) | KA 34/800-BSY+ R (M2) | KA 34/800-BSY+ L (S1) | KA 34/1000-BSY+ R (M2) | KA 34/1000-BSY+ L (S1) | |
---|---|---|---|---|---|---|---|---|---|---|
Supply | 24 V DC / ±15 % / 1 A | 24 V DC / ±15 % / 1 A | 24 V DC / ±15 % / 1 A | 24 V DC / ±15 % / 1 A | 24 V DC / ±15 % / 1 A | 24 V DC / ±15 % / 1 A | 24 V DC / ±15 % / 1 A | 24 V DC / ±15 % / 1 A | 24 V DC / ±15 % / 1 A | |
Duty cycle | Variable designs possible | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) |
Force of pressure | 300 N | 300 N | 300 N | 300 N | 300 N | 300 N | 300 N | 300 N | 300 N | |
Tensile force | 300 N | 300 N | 300 N | 300 N | 300 N | 300 N | 300 N | 300 N | 300 N | |
Nominal locking force ** | Max. 2600 N (2000 N ***) | Max. 2600 N (2000 N ***) | Max. 2600 N (2000 N ***) | Max. 2600 N (2000 N ***) | Max. 2600 N (2000 N ***) | Max. 2600 N (2000 N ***) | Max. 2600 N (2000 N ***) | Max. 2600 N (2000 N ***) | Max. 2600 N (2000 N ***) | |
Service life | 20000 double strokes * | 20000 double strokes * | 20000 double strokes * | 20000 double strokes * | 20000 double strokes * | 20000 double strokes * | 20000 double strokes * | 20000 double strokes * | 20000 double strokes * | |
Stroke | - | 600 mm | 600 mm | 700 mm | 700 mm | 800 mm | 800 mm | 1000 mm | 1000 mm | |
OPEN running speed | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | |
OPEN running speed - SHEV | 12.2 mm/s | 12.2 mm/s | 12.2 mm/s | 12.2 mm/s | 12.2 mm/s | 12.2 mm/s | 12.2 mm/s | 12.2 mm/s | 12.2 mm/s | |
CLOSED running speed | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | |
Show more information
|
||||||||||
Request & Compare |
KA-BSY+ |
KA 34-BSY+
|
KA 34/600-BSY+ R (M2)
|
KA 34/600-BSY+ L (S1)
|
KA 34/700-BSY+ R (M2)
|
KA 34/700-BSY+ L (S1)
|
KA 34/800-BSY+ R (M2)
|
KA 34/800-BSY+ L (S1)
|
KA 34/1000-BSY+ R (M2)
|
KA 34/1000-BSY+ L (S1)
|
Configure now |
* For vertical use, please consult with D+H Sales!
** Depending on the mounting, *** in accordance with VdS 2580
Specification per drive